Step 1 — Determine the Load (NEC 215.2)
Before looking at wire tables, define the circuit load. Continuous loads, such as lighting or EV charging, must be multiplied by 125%. Non-continuous loads use 100%. [Source: NEC 215.2]
Select the correct conductor size for ampacity and conditions.
Calculating wire sizing in the 2023 NEC is a multi-step process. You cannot simply pick a wire size — you must satisfy three main criteria: Ampacity, Voltage Drop, and Terminal Temperature Ratings. [Source: NEC 110.14(C), 210.19(A), 215.2, 310.15, and 310.16]
Before looking at wire tables, define the circuit load. Continuous loads, such as lighting or EV charging, must be multiplied by 125%. Non-continuous loads use 100%. [Source: NEC 215.2]
This is a common point of failure. Most equipment is limited by its terminal rating, so the selected ampacity column must match the lowest temperature rating of the equipment, conductor, and termination. [Source: NEC 110.14(C)]
Using the total load and the correct temperature column from Table 310.16, select a conductor size with ampacity equal to or greater than the calculated load. [Source: NEC 310.16]
De-rate the wire when ambient temperature exceeds standard conditions or when more than three current-carrying conductors share a raceway or cable. [Source: NEC 310.15]
Use voltage drop as a design check after ampacity is satisfied. If voltage drop is too high, upsize the conductor even when the ampacity table appears acceptable. [Source: NEC 210.19(A) Informational Note]
The answers we give you are for educational purposes only. Please verify with your code book, your journeyman or master electrician, and your local Authority Having Jurisdiction (AHJ).